Geothermal Heating & Cooling Terminology
With over 4,500 installs
Harrisburg, PA Free Quote
Tribute to Jim Boban
Miss You Jim
4 Ton 2 Stage Geothermal Heating And Cooling Heat Pump - $6,145.00
Retail Price: $6,155.00
You Save: $10.00
Bosch
FHP Manufacturing
Climate Master
Addison Products
Bard Manufacturing
Commandaire
ECONAR
ECR Technologies
GeoComfort
HydroHeat, LLC
Hydron Module
Hydro-Temp
Mammoth, Inc.
McQuay
WaterFurnace
Flow Center Products
Thermcosupply.com
Geothermal Supply Co.
Integrity Fusion
AEPCOR-Geothermal
Morris Industries
BlueRidgeCompany
Geo-Hydro Supply, LLC
air conditioner servicing directory
IGSHPA
Dept. of Energy
ENERGY STAR
The first recorded
geothermal system
was a
1912 Swiss patent.
geothermal system
was a
1912 Swiss patent.
Current geothermal
heating and cooling
saves more than
14 million barrels
of crude oil per year.
heating and cooling
saves more than
14 million barrels
of crude oil per year.
These pages will help with your heating and cooling problems!
- Diagrams
- Repair
- Installations
- Terminology
- Filters
- Articles
Case Study.pdf Download HVAC-Calc Residential Manual J Software Download NATURAL REFRIGERANT CO2.PDF Download U.S. Solar Heating Electric Duct Comparison.PDF Download Energy Cost Calc.xlr Download R S Means Mechanical Cost Data.mht Download Leaky Ducts.docx Download Residential Duct Systems.pdf Download Planning for a Nuclear Detonation .pdf Download
A new message and message archive with a few repair notes
Active Cooling - Compressor driven air-conditioning.
Amps - Current (back up excluded)
BTU - British Thermal Unit - The amount of heat required to raise the temperature of one pound of water, one degree Fahrenheit.
Coefficient of Performance (COP) - Heating capacity divided by electrical energy consumed. (e.g.15 kW output / 4.5 kW input = COP of 3.3) The coefficient of performance of a heating system is the electrical ratio of the heat we get out divided by the heat we put in.
Condenser - The heat rejecting mechanism in a heat pump usually in the form of a refrigerant-to-air coil or a refrigerant-to-water coil. Refrigeration heat exchanger where the refrigerant gives up its heat during condensation from a vapor to a liquid.
Compressor - Refrigeration component which increases the density, temperature and pressure of entering refrigerant through compression and discharges a hot dense gas.
Closed Loop - An underground heat exchanger piping system usually of polyethylene or polybutylene designed to allow the extraction or rejection of heat to the earth by the circulation of fluid within the tubing.
Check Valve - A check valve is a mechanical device normally applied to a piping system which allows fluid to flow in only one direction.
CFM - Cubic feet per minute of air flow.
Cupro-nickel - 90% copper / 10% nickel alloy which has high corrosion resistance to water containing salt, sulphur, chlorides and other dissolved minerals.
Cond. - Freon temperature on condenser side.
Comp.-Wats - Compressor electricity consumption.
Degree Day - The number of degrees that the mean temperature for that day is below 65 degrees F. (e.g. mean temp. of 40 degrees F for the day--65-40=25 degree days)
Desuperheater - A heat exchanger and pump system which removes a small portion of heat from the compressor discharge gas and typically transfers it to a domestic hot water tank.
Direct Expansion Heat Pump - A geothermal heat pump system whereby the liquid refrigerant is sent directly out into copper coils buried in the ground where it is vaporized or condensed by contact with the earth.
Dual Condenser - A heat pump system which has the capability to switch, usually automatically, between an air and a water heat exchanger. Full capacity hot air or hot water output is available.
Delta T. - Difference in-between LWT and EWT
Energy Efficiency Ratio (EER) - Cooling capacity in BTU/hr divided by electrical energy consumed in watts.
EWT - Entering water or fluid temperature.
ELT - Entering liquid temperature.
EAT - Entering air temperature.
EER - Energy efficiency ratio.
Evaporator - The heat absorbing mechanism or heat exchanger in a heat pump. Refrigerant changes phase from a liquid to a gas in this exchanger, absorbing heat energy from the surrounding media in the process.
Evap. T. - The temperature on evaporator side when Freon is converted from a liquid to a vapor (gas)
Freon - Trade name for a series of man made chemicals or refrigerants used in refrigeration systems. Each refrigerant is designed to change phase at specific temperatures and pressures which will produce the desired cooling effect required for a specific job. The refrigerant absorbs energy as it evaporates and releases energy during condensation.
Full Package - Self contained heat pump which has blower and compressor section integrated into one unit.
Full-Condensing Heat Exchanger - A heat exchanger with enough surface area to condense all the hot refrigerant gas produced by a heat pump to it's liquid state thereby transferring the all the heat produced by the unit.
Flow IGPM - Liquid flow.
Fan-Watts - Blower motor electricity consumption.
Geothermal Energy - Heat energy stored in the earth's crust by the absorption of solar energy and by conduction with the earth's hot interior.
Ground Loop - A series of heat exchange pipes containing an antifreeze solution which are buried either vertically or horizontally in the earth.
Ground Source - A heat pump which utilizes the earth as it's source of energy.
Heat Exchanger - A component which transfers heat energy from one medium to another. For example heat could be transferred, in a geothermal heat pump system, from water-to-air or from water-to-water etc. and vice versa.
Heat Source - The area or media from which heat is removed. (water, air, etc.)
Heat sink - The area or media where heat is deposited. (Inside a home, etc.)
HAB - Heating mode: heat absorption capacity from the ground or water - Cooling mode: heat absorption capacity from the inside air (total cooling load)
IGPM - Water flow in Imperial Gallons
KWH - Kilowatt hours - Electrical term - 1 Kwh equals the use of 1000 watts for one hour.
KW OUT - Heat pump capacity in KW's
Liquid-to-Air Heat Pump - A heat pump which absorbs heat from a liquid and distributes the energy in the form of hot forced air.
Liquid-to-Liquid heat pump - A heat pump which absorbs heat from a liquid and distributes the energy in the form of hot water.
LWT - Leaving water temperature.
LAT - Leaving air temperature.
LLT - Leaving liquid temperature.
Latent - The load created by moisture in the air, including from outside air infiltration and that from indoor sources such as occupants, plants, cooking, showering, etc.
Mechanical Cooling - Conventional cooling provided by a compressor operated refrigeration device. Term can be interchanged with "active cooling".
Open Loop - A system where water is pumped from a water well, pond, lake or other surface source for use in a heat pump.
Oversized Evaporator - A technique of employing a larger than normal evaporator (heat absorption device) in a geothermal heat pump in order to obtain greater heat exchange and thus better performance from the unit.
Output - Heat pump capacity in Btu's/Ton's.
Passive Cooling - A process whereby cold well water (less than 50 degrees F.) is pumped directly to a finned air coil (much like the radiator of a car) so that when the heat pump fan is operated, cooling and dehumidification are provided without the operation of a compressor driven refrigeration system.
Package Heat Pump - A heat pump which has all components (compressor, blower and heat exchangers etc.) in one cabinet.
Refrigerant - A naturally occurring or man made liquid which absorbs and releases heat energy in a refrigeration device by changing phase from a liquid to a gas and vise versa in response to the influence of a refrigeration compressor.
Reversing Heat Pump - A heat pump in which the condenser and evaporator coils of the unit reverse roles in response to a reverse in the direction of the flow of refrigerant in the machine
Radiant Floor Heating - Process of embedding tubing (cross-linked polyethylene, polybutylene etc.) directly in a concrete floor so that hot water can be pumped through the tubing for the purpose of heating the floor and thus the building.
Seasonal Coefficient of Performance (SCOP) - Is the average COP over the entire heating season.
Seasonal Energy Efficiency Ratio (SEER) -The average cooling efficiency over an entire cooling season.
Simple Payback Factor (heating) - Subtract the installation cost of the least expensive (less efficient) system from the installation cost of the more expensive (more efficient) heating system. This value is the increased cost of installing the more efficient system. Calculate the yearly energy savings in dollars by installing the more efficient system. Take the increased cost to install divided by the yearly energy savings and your result is the number of years required for the more efficient system to pay for itself.
Sink Temperature - This is the temperature of the media (water or air) into which the heat pump must reject it's heat.
Source Temperature - This is the temperature of the media (water or air) from which the heat pump extracts its heat.
Split System - Split heat pumps are two (2) part refrigeration systems which have separate evaporator / air handler and compressor / condenser sections. Commonly employed in air-to-air systems where the condenser section is located outside the home while the evaporator / air handler is located inside the conditioned structure.
Sensible - The interior heat gain due to heat conduction, convection, and radiation from the exterior into the interior, and from occupants and appliances.
TX Valve - A temperature and pressure controlled device for metering refrigerant in a heat pump or other refrigeration device.
Ton (of refrigeration) - The amount of energy it takes to convert 2000 lbs. of water at 32 degrees F. to ice at 32 degrees F. during a 24 hour period. Calculation: 2000 lbs.H2O x 144
Btu/lb. = 288,000 Btu's in 24 Hrs. Divide by 24 hrs = 12,000 Btu/hr. Therefore a "ton" of cooling is a measure of heat energy which is roughly equivalent to 12,000 BTU's.
Turbotec - Trade name for a high efficiency expanded surface style coaxial tube-in-tube heat exchanger.
Temp. diff. - Difference between ELT and a LLT.
Water Well - A vertical bore hole into the earths crust usually to a depth of less than 300 ft. for the purpose of accessing an underground water supply (aquifer). A pumping system generally of the submersible type is normally installed to bring the water to the surface under sufficient pressure to be used in a home.
Water-to-Water - A heat pump which extracts heat from water in one area and transfers the heat usually at a higher temperature to another body of water. ex. extracting heat from a 50 degrees F. well and using it to heat domestic hot water at 120 degrees F
Geothermal Heating & Cooling Terminology
Commonly Used Terminology in Geothermal Heating and Cooling
Aquifer - A large body of underground water.Active Cooling - Compressor driven air-conditioning.
Amps - Current (back up excluded)
BTU - British Thermal Unit - The amount of heat required to raise the temperature of one pound of water, one degree Fahrenheit.
Coefficient of Performance (COP) - Heating capacity divided by electrical energy consumed. (e.g.15 kW output / 4.5 kW input = COP of 3.3) The coefficient of performance of a heating system is the electrical ratio of the heat we get out divided by the heat we put in.
Condenser - The heat rejecting mechanism in a heat pump usually in the form of a refrigerant-to-air coil or a refrigerant-to-water coil. Refrigeration heat exchanger where the refrigerant gives up its heat during condensation from a vapor to a liquid.
Compressor - Refrigeration component which increases the density, temperature and pressure of entering refrigerant through compression and discharges a hot dense gas.
Closed Loop - An underground heat exchanger piping system usually of polyethylene or polybutylene designed to allow the extraction or rejection of heat to the earth by the circulation of fluid within the tubing.
Check Valve - A check valve is a mechanical device normally applied to a piping system which allows fluid to flow in only one direction.
CFM - Cubic feet per minute of air flow.
Cupro-nickel - 90% copper / 10% nickel alloy which has high corrosion resistance to water containing salt, sulphur, chlorides and other dissolved minerals.
Cond. - Freon temperature on condenser side.
Comp.-Wats - Compressor electricity consumption.
Degree Day - The number of degrees that the mean temperature for that day is below 65 degrees F. (e.g. mean temp. of 40 degrees F for the day--65-40=25 degree days)
Desuperheater - A heat exchanger and pump system which removes a small portion of heat from the compressor discharge gas and typically transfers it to a domestic hot water tank.
Direct Expansion Heat Pump - A geothermal heat pump system whereby the liquid refrigerant is sent directly out into copper coils buried in the ground where it is vaporized or condensed by contact with the earth.
Dual Condenser - A heat pump system which has the capability to switch, usually automatically, between an air and a water heat exchanger. Full capacity hot air or hot water output is available.
Delta T. - Difference in-between LWT and EWT
Energy Efficiency Ratio (EER) - Cooling capacity in BTU/hr divided by electrical energy consumed in watts.
EWT - Entering water or fluid temperature.
ELT - Entering liquid temperature.
EAT - Entering air temperature.
EER - Energy efficiency ratio.
Evaporator - The heat absorbing mechanism or heat exchanger in a heat pump. Refrigerant changes phase from a liquid to a gas in this exchanger, absorbing heat energy from the surrounding media in the process.
Evap. T. - The temperature on evaporator side when Freon is converted from a liquid to a vapor (gas)
Freon - Trade name for a series of man made chemicals or refrigerants used in refrigeration systems. Each refrigerant is designed to change phase at specific temperatures and pressures which will produce the desired cooling effect required for a specific job. The refrigerant absorbs energy as it evaporates and releases energy during condensation.
Full Package - Self contained heat pump which has blower and compressor section integrated into one unit.
Full-Condensing Heat Exchanger - A heat exchanger with enough surface area to condense all the hot refrigerant gas produced by a heat pump to it's liquid state thereby transferring the all the heat produced by the unit.
Flow IGPM - Liquid flow.
Fan-Watts - Blower motor electricity consumption.
Geothermal Energy - Heat energy stored in the earth's crust by the absorption of solar energy and by conduction with the earth's hot interior.
Ground Loop - A series of heat exchange pipes containing an antifreeze solution which are buried either vertically or horizontally in the earth.
Ground Source - A heat pump which utilizes the earth as it's source of energy.
Heat Exchanger - A component which transfers heat energy from one medium to another. For example heat could be transferred, in a geothermal heat pump system, from water-to-air or from water-to-water etc. and vice versa.
Heat Source - The area or media from which heat is removed. (water, air, etc.)
Heat sink - The area or media where heat is deposited. (Inside a home, etc.)
HAB - Heating mode: heat absorption capacity from the ground or water - Cooling mode: heat absorption capacity from the inside air (total cooling load)
IGPM - Water flow in Imperial Gallons
KWH - Kilowatt hours - Electrical term - 1 Kwh equals the use of 1000 watts for one hour.
KW OUT - Heat pump capacity in KW's
Liquid-to-Air Heat Pump - A heat pump which absorbs heat from a liquid and distributes the energy in the form of hot forced air.
Liquid-to-Liquid heat pump - A heat pump which absorbs heat from a liquid and distributes the energy in the form of hot water.
LWT - Leaving water temperature.
LAT - Leaving air temperature.
LLT - Leaving liquid temperature.
Latent - The load created by moisture in the air, including from outside air infiltration and that from indoor sources such as occupants, plants, cooking, showering, etc.
Mechanical Cooling - Conventional cooling provided by a compressor operated refrigeration device. Term can be interchanged with "active cooling".
Open Loop - A system where water is pumped from a water well, pond, lake or other surface source for use in a heat pump.
Oversized Evaporator - A technique of employing a larger than normal evaporator (heat absorption device) in a geothermal heat pump in order to obtain greater heat exchange and thus better performance from the unit.
Output - Heat pump capacity in Btu's/Ton's.
Passive Cooling - A process whereby cold well water (less than 50 degrees F.) is pumped directly to a finned air coil (much like the radiator of a car) so that when the heat pump fan is operated, cooling and dehumidification are provided without the operation of a compressor driven refrigeration system.
Package Heat Pump - A heat pump which has all components (compressor, blower and heat exchangers etc.) in one cabinet.
Refrigerant - A naturally occurring or man made liquid which absorbs and releases heat energy in a refrigeration device by changing phase from a liquid to a gas and vise versa in response to the influence of a refrigeration compressor.
Reversing Heat Pump - A heat pump in which the condenser and evaporator coils of the unit reverse roles in response to a reverse in the direction of the flow of refrigerant in the machine
Radiant Floor Heating - Process of embedding tubing (cross-linked polyethylene, polybutylene etc.) directly in a concrete floor so that hot water can be pumped through the tubing for the purpose of heating the floor and thus the building.
Seasonal Coefficient of Performance (SCOP) - Is the average COP over the entire heating season.
Seasonal Energy Efficiency Ratio (SEER) -The average cooling efficiency over an entire cooling season.
Simple Payback Factor (heating) - Subtract the installation cost of the least expensive (less efficient) system from the installation cost of the more expensive (more efficient) heating system. This value is the increased cost of installing the more efficient system. Calculate the yearly energy savings in dollars by installing the more efficient system. Take the increased cost to install divided by the yearly energy savings and your result is the number of years required for the more efficient system to pay for itself.
Sink Temperature - This is the temperature of the media (water or air) into which the heat pump must reject it's heat.
Source Temperature - This is the temperature of the media (water or air) from which the heat pump extracts its heat.
Split System - Split heat pumps are two (2) part refrigeration systems which have separate evaporator / air handler and compressor / condenser sections. Commonly employed in air-to-air systems where the condenser section is located outside the home while the evaporator / air handler is located inside the conditioned structure.
Sensible - The interior heat gain due to heat conduction, convection, and radiation from the exterior into the interior, and from occupants and appliances.
TX Valve - A temperature and pressure controlled device for metering refrigerant in a heat pump or other refrigeration device.
Ton (of refrigeration) - The amount of energy it takes to convert 2000 lbs. of water at 32 degrees F. to ice at 32 degrees F. during a 24 hour period. Calculation: 2000 lbs.H2O x 144
Btu/lb. = 288,000 Btu's in 24 Hrs. Divide by 24 hrs = 12,000 Btu/hr. Therefore a "ton" of cooling is a measure of heat energy which is roughly equivalent to 12,000 BTU's.
Turbotec - Trade name for a high efficiency expanded surface style coaxial tube-in-tube heat exchanger.
Temp. diff. - Difference between ELT and a LLT.
Water Well - A vertical bore hole into the earths crust usually to a depth of less than 300 ft. for the purpose of accessing an underground water supply (aquifer). A pumping system generally of the submersible type is normally installed to bring the water to the surface under sufficient pressure to be used in a home.
Water-to-Water - A heat pump which extracts heat from water in one area and transfers the heat usually at a higher temperature to another body of water. ex. extracting heat from a 50 degrees F. well and using it to heat domestic hot water at 120 degrees F
Geothermal Heating & Cooling Terminology